Chapter 12 · Mississippi Waterworks Operators Manual

Cross-Connection Control

How contaminated water can flow backward into the drinking-water system โ€” and the five devices that stop it.

Greg's take on this chapter

Match the device to the hazard, every time โ€” that's the whole game in this chapter. Air gap for the worst hazards, RPZ when an air gap isn't practical, double-check for low-to-intermediate non-health hazards, and vacuum breakers only where there's no back-pressure risk. Get that hierarchy locked in.

1 Cross connections and backflow

A cross connection is any piping arrangement connecting a potable line to potentially contaminated water โ€” either pipe-to-pipe, or a potable outlet submerged in contaminated water. Most happen unintentionally; a gate or check valve alone doesn't count as protection since they can leak undetected. Backflow is what happens when that connection reverses flow direction, letting contamination into the potable system. There are two causes:

  • Back pressure โ€” the contaminated side's pressure exceeds the potable line's pressure (e.g., non-potable water pumped or stored at a higher elevation).
  • Back-siphonage โ€” a vacuum forms in the water line (from a main break or nearby firefighting) and draws contaminated water in.

Hazard is classed high (could cause death, illness, or spread disease) or low (a nuisance, not a health hazard) โ€” and the toxicity of the potential contaminant is what actually drives device selection.

2 The five backflow-prevention devices

DeviceProtects againstBest for
Air gap (AG)BothAny toxic hazard; physical separation, โ‰ฅ 2ร— pipe diameter, never less than 1 inch
Atmospheric vacuum breaker (AVB)Back-siphonage onlyNon-continuous-pressure uses (hose bibs, sprinklers) โ€” must sit 12" above highest use point
Pressure vacuum breaker (PVB)Back-siphonage onlySame uses as AVB, but works under continuous pressure
Double check valve assembly (DC)BothLow-to-intermediate (polluted, not contaminated) hazards; head loss usually < 10 psi
Reduced pressure zone (RPZ)BothHigh-hazard installations where an air gap isn't practical; head loss 10-20 psi

All backflow-prevention devices need annual testing. An RPZ works via two spring-loaded check valves with a relief valve between them โ€” if the second check valve fails, the relief valve vents to atmosphere rather than letting contamination back into the system, and a bypass line around an RPZ must also contain its own RPZ.

3 Whose job is it?

Everyone shares responsibility:

  • The customer โ€” owns everything from the meter to the sewer, and must install/test/maintain backflow prevention at their own expense if a cross connection exists.
  • The water supplier โ€” responsible from the source through the entire distribution system up to the meter: surveying regularly, educating the public, eliminating cross connections, and maintaining at least 20 psi to reduce back-siphonage risk.
  • The plumber โ€” the first line of defense, catching potential cross connections during installation and reporting them immediately.
  • MSDH โ€” enforces the rules and ensures water suppliers run adequate internal-protection and backflow-prevention programs.

4 Common hazards and the right protection

WhereHazardTypical protection
Lawn irrigationFertilizer, pesticides, animal wastePVB or RPZ; RPZ if chemicals are injected
Boilers and cooling towersTreatment chemicals and back pressureRPZ
Hospitals, labs, mortuariesPathogens and chemicalsRPZ at the service (containment)
Car washes and chemical plantsDetergents and chemicalsRPZ or air gap
Fire sprinkler systemsStagnant water; antifreeze or additives in some systemsDouble check assembly; RPZ if chemicals are added
Garden hosesBack-siphonage from buckets, sprayers, and poolsHose bib vacuum breaker
Tanks, vats, and chemical feedWhatever is in the tankAir gap

Local codes and MSDH set the final requirement. When in doubt, protect for the higher hazard.

5 Testing backflow assemblies

Testable assemblies (the PVB, double check, and RPZ) must be tested by a certified tester when installed, at least once a year, and after any repair or relocation. The tester connects a differential pressure gauge to the test cocks and checks each part. Typical passing values in common test procedures:

  • RPZ: the relief valve opens with at least 2 psid across the first check, the first check holds at least 5 psid, and the second check is tight against back pressure.
  • Double check: each check valve holds at least 1 psid.
  • PVB: the air inlet opens at 1 psid or more, and the check holds at least 1 psid.

A failed assembly is repaired and retested right away. Keep a record of every test for each assembly: the date, tester, readings, and repairs.

6 Running a cross-connection control program

  1. Get the authority: an ordinance or policy that lets the utility require devices and shut off service for noncompliance.
  2. Survey customers, starting with high hazards such as hospitals, industries, car washes, and irrigation systems.
  3. Require protection: containment at the meter for high hazards, plus internal protection under the plumbing code.
  4. Track testing: keep a list of every assembly, send annual test reminders, and follow up on overdue tests.
  5. Educate customers and plumbers about backflow, especially hoses and irrigation.
  6. Enforce: after notice, discontinue service when a customer refuses to correct a hazard.

One side effect to explain to customers: a check valve or backflow assembly at the meter makes a closed system. When a water heater warms water, the water expands with nowhere to go and the pressure rises. A thermal expansion tank solves it.

๐Ÿ“Œ Numbers Greg wants you to memorize

  • Air gap: at least 2ร— the supply pipe diameter, never less than 1 inch.
  • All backflow devices require annual testing.
  • AVB/PVB must sit at least 12 inches above the highest point of use.
  • Double-check assembly head loss: usually under 10 psi; RPZ head loss: 10-20 psi.
  • Maintain at least 20 psi distribution pressure to reduce back-siphonage risk.
  • RPZ test: relief valve opens at โ‰ฅ 2 psid; first check holds โ‰ฅ 5 psid.
  • Double check and PVB checks hold โ‰ฅ 1 psid.
  • AVB: no more than 12 hours of continuous pressure in any 24.
Key terms

Words to know for Chapter 12

Plain-language definitions from the LearnWater glossary.

Open the full glossary โ†’

Check yourself

Quick check: 5 questions

Random questions from this chapter's bank. Your answers count toward your progress in the Learning Center.

Flash cards

Tap a card to flip it

Study these in the flash card trainer โ†’

Ask Greg

Questions about Chapter 12?

Greg answers from the operators manual and works formulas right in your browser. Ask him to search EPA, NRWA, or MsRWA and only your search words go to that site.

Finished this chapter?Mark it complete to update your progress.