Greg's take on this chapter
This is the chapter that makes the treatment chapters make sense. Get pH backwards (low number = acidic, more H⁺ ions) locked in, know the hardness ranges, and understand why alkalinity matters so much for coagulation. It's not hard chemistry — it's mostly vocabulary and a couple of key relationships.
1 Ions and pH
Dissolved materials separate into electrically charged particles called ions. pH measures hydrogen ion (H⁺) concentration on a scale of 0 to 14: as H⁺ increases, pH goes down. Pure water has equal H⁺ and OH⁻ concentrations at pH 7 — neutral. Below 7 is acidic, above 7 is alkaline/basic.
Chlorine, alum, ferric sulfate, sulfuric acid, hydrofluosilicic acid, and carbon dioxide all lower pH. Lime, soda ash, sodium hydroxide (caustic soda), and hypochlorite all raise pH. Many Mississippi ground waters run low pH naturally because of dissolved carbon dioxide, which aeration can remove.
2 Alkalinity
Alkalinity measures water's ability to neutralize acid — increasing alkalinity raises pH and buffers it against swings. It comes mainly from hydroxide, carbonate, and bicarbonate ions, with bicarbonate providing most of it in natural water. Alkalinity is critical for coagulation: most ground water in Mississippi has enough natural alkalinity for coagulation to work, but some needs lime added first — always dosed separately from the coagulant, since lime and alum react with each other directly.
3 Hardness
Hardness is caused mainly by calcium and magnesium ions (also strontium, iron, manganese, aluminum). The Mississippi guideline scale:
| Classification | mg/l as CaCO₃ |
|---|---|
| Soft | under 75 |
| Moderately soft/hard | 75-150 |
| Hard | 150-200 |
| Very hard | over 200 |
Carbonate (temporary) hardness can be removed just by heat, which drives off CO₂ and precipitates carbonate. Non-carbonate (permanent) hardness doesn't respond to heat and forms hard scale once its solubility limit is exceeded. Rule of thumb: where total alkalinity is equal to or greater than total hardness, all the hardness is carbonate; where alkalinity is less than hardness, the carbonate hardness equals the alkalinity and the rest is non-carbonate.
4 Coagulation chemistry
Coagulants react with alkalinity to form hydroxide floc (aluminum hydroxide, ferric hydroxide) that traps microorganisms, color, and turbidity as it settles. The standard tool for dialing in the right dose is the jar test: fill several jars with test water, add varying coagulant amounts, mix vigorously briefly then gently for a longer period to let floc form, then check settled water for color and turbidity to find the best dose, mixing time, and settling time.
5 Iron, manganese, and hydrogen sulfide
In the oxygen-free water deep in an aquifer, iron and manganese stay dissolved and invisible (ferrous iron, Fe²⁺, and manganous manganese, Mn²⁺). Once the water meets air or an oxidant, they turn into solid particles that stain: reddish-brown for iron, black for manganese. That's why clear well water can turn red in a glass or a toilet tank.
Oxidants react in fixed proportions, so you can estimate how much you'll need:
| To oxidize 1 mg/L of | Chlorine | Potassium permanganate |
|---|---|---|
| Iron | about 0.6 mg/L | about 0.9 mg/L |
| Manganese | about 1.3 mg/L | about 1.9 mg/L |
Iron oxidizes quickly, but chlorine oxidizes manganese slowly unless the pH is high, which is why permanganate or greensand is often used for manganese. Hydrogen sulfide gives water a rotten-egg odor, corrodes metal, and uses up chlorine (the manual's figure is 2.1 mg/L of chlorine per mg/L of H₂S). Aeration removes much of it, especially at lower pH, where more of it is in its gas form.
6 Corrosion and lead
Corrosive water eats pipe from the inside, causing leaks, red water, and lead and copper dissolving from service lines, solder, and brass fixtures. Water tends to be corrosive when it has:
- low pH (below about 7)
- low alkalinity and hardness (soft water)
- high dissolved oxygen or carbon dioxide
- high chloride or sulfate
Treatment options include raising pH and alkalinity with lime, soda ash, or caustic soda; feeding orthophosphate to form a protective film; and adjusting the water so it lays down a thin calcium carbonate coating (a slightly positive Langelier index).
The Lead and Copper Rule checks how well this works with first-draw tap samples from high-risk homes: one liter from a tap that has sat unused for at least six hours. If more than 10% of samples exceed the lead action level (15 µg/L, dropping to 10 µg/L under the 2024 improvements) or the copper action level (1.3 mg/L), the system must take added steps, including corrosion control treatment and public education.
7 Everyday water tests
| Test | How it's done | Tips |
|---|---|---|
| pH | pH meter with a glass electrode | Calibrate daily with fresh buffers (usually pH 7 plus pH 4 or 10), and keep the electrode wet |
| Chlorine residual | DPD color test or colorimeter | Read free chlorine within about a minute; total = free + combined |
| Alkalinity | Titrate with sulfuric acid to an end point near pH 4.5 | Report as mg/L CaCO₃ |
| Hardness | EDTA titration; the indicator turns from wine-red to blue | Report as mg/L CaCO₃ |
| Iron and manganese | Colorimetric test kits | Test before and after treatment to see what's being removed |
| Fluoride | Ion-selective electrode or SPADNS color method | Test daily if you fluoridate |
| Turbidity | Turbidimeter, in NTU | Use clean, unscratched sample cells and calibrate with standards |
Good lab habits matter as much as the method: rinse glassware with sample water first, check reagent expiration dates, and log every result with the time and location.
📌 Numbers Greg wants you to memorize
- pH scale: 0-14, with 7 = neutral. Lower pH = more H⁺ ions = more acidic.
- Hardness: soft <75, moderate 75-150, hard 150-200, very hard >200 mg/l as CaCO₃.
- Bicarbonate provides most natural alkalinity in Mississippi ground water.
- Never mix lime and coagulant in the same feed line — add lime first, separately.
- Chlorine needed to oxidize 1 mg/L iron ≈ 0.6 mg/L; manganese ≈ 1.3 mg/L.
- Lead and copper samples: 1-liter first draw after at least 6 hours unused.
- Action levels: copper 1.3 mg/L; lead 15 µg/L (10 µg/L under the LCRI).
Words to know for Chapter 7
Plain-language definitions from the LearnWater glossary.
Quick check: 5 questions
Random questions from this chapter's bank. Your answers count toward your progress in the Learning Center.
Tap a card to flip it
Questions about Chapter 7?
Greg answers from the operators manual and works formulas right in your browser. Ask him to search EPA, NRWA, or MsRWA and only your search words go to that site.