Chapter 4 · Mississippi Waterworks Operators Manual

Hydraulics

How water at rest and in motion behaves — static and dynamic head, pressure, friction loss, flow measurement, and pumps.

Greg's take on this chapter

Hydraulics questions almost always reduce to one conversion: 1 foot of water = 0.433 psi, or flip it around and 1 psi = 2.31 feet of water. Learn that cold and you can answer most static-head questions in your head. Then know the difference between centrifugal and positive-displacement pumps — that distinction shows up constantly.

1 Static head and pressure

Static head (elevation head) is the level of water above a reference elevation, measured in feet — it represents potential energy. With no water moving, levels equalize to match the highest elevated tank or standpipe in the system. To find static head at a point, subtract that point's elevation from the system's highest water elevation.

Water weighs 62.4 lbs per cubic foot. Work through the math on a one-square-foot column of water one foot tall, and you get the single most useful number in this whole chapter: 1 foot of water = 0.433 psi. Flip it around (1 ÷ 0.433) and 1 psi = 2.31 feet of water. This holds no matter the shape of the container — pressure depends only on height of water above the measurement point, never on the container's shape.

2 Dynamic hydraulics and head loss

Total head in a flowing system = elevation (static) head + velocity head + pressure head (the Bernoulli principle). Velocity head is usually small in distribution systems, since design velocities stay under 5 ft/sec to limit friction loss. As water moves through pipe, some head is lost to friction — from water molecules rubbing the pipe wall and each other, and from bends, valves, and fittings. This is friction head loss, and it's why pressure head in a moving system is always less than static head.

Friction loss depends on flow rate, pipe diameter and length, and pipe roughness — captured by the Hazen-Williams C-factor. New PVC pipe has a C of about 150; new ductile iron about 130; old tuberculated cast iron can drop to 50 or lower. The rougher the pipe, the lower the C-factor and the higher the friction loss.

3 Flow measurement

Metering matters because unaccounted-for water — the gap between what's pumped and what's billed — signals leaks and unmetered usage. Common flow-measuring devices include the residential displacement meter, the venturi meter (which the chlorinator ejector also relies on), the orifice/weir plate, and magnetic flow meters that measure the voltage induced as water passes through a magnetic field. Rate-of-flow controllers use the venturi principle to hold a filter's flow rate steady.

4 Pumps

Water-system pumps fall into two families:

  • Positive displacement pumps (piston or rotary) deliver a constant volume regardless of downstream conditions. They're mainly used for feeding chemical solutions in small plants — simple, reliable, easy to maintain — but the pump will keep trying to force water even against a closed valve, which can rupture the discharge line or diaphragm if not protected.
  • Centrifugal pumps use a spinning impeller to fling water outward by centrifugal force, creating low pressure at the center that draws more water in. They must be primed (air in the casing stops them from pumping), give nonpulsating flow, need no internal valves, and have one point of peak efficiency on their head-discharge curve — the "characteristic curve" the operator should try to run near.

5 Total dynamic head and horsepower

A pump has to overcome total dynamic head (TDH): the vertical lift, plus friction losses, plus any pressure it must deliver at the discharge, all in feet. Convert pressure with 2.31 ft/psi. A well pump that lifts water 180 feet to the surface, delivers 50 psi into the system, and loses 15 feet to friction works against 180 + 15 + (50 × 2.31) = 310 feet of TDH.

Horsepower follows from flow and head:

  • Water horsepower = gpm × TDH (ft) ÷ 3,960
  • Brake horsepower = water horsepower ÷ pump efficiency
  • Motor horsepower = brake horsepower ÷ motor efficiency
  • 1 horsepower = 0.746 kilowatts

Example. 500 gpm against 150 feet of TDH: water horsepower = 500 × 150 ÷ 3,960 = 18.9 hp. With a 75% efficient pump, brake horsepower = 25.3 hp. With a 90% efficient motor, motor horsepower = 28.1 hp, about 21 kW. Running 24 hours at $0.10 per kWh, that pump costs about $50 a day.

6 Pump curves, affinity laws, and pumps working together

A centrifugal pump's curve shows how much head it makes at each flow. At zero flow it makes its highest head, the shutoff head; as flow rises, head drops. The system has a curve too (static lift plus friction, which grows with flow), and the pump always runs where the two curves cross. Pick pumps so that point lands near the best efficiency point.

When a pump's speed changes, as with a variable frequency drive, the affinity laws predict the result: flow changes in proportion to speed, head with the speed squared, and power with the speed cubed. Slowing a pump to 80% speed gives about 80% of the flow, 64% of the head, and 51% of the power.

Two pumps in series (one feeding the next) add their heads at the same flow, so series pumping reaches higher pressure. Two pumps in parallel (side by side into one header) add their flows at the same head, although the combined flow is usually less than double because friction rises with flow.

7 Keeping pumps healthy

  • Prime it. A centrifugal pump can't move air. Fill the casing and suction line before starting, and never let it run dry.
  • Watch the packing. Packing should leak a slow, steady drip to cool and lubricate the shaft. Tighten the gland evenly, a little at a time. Mechanical seals shouldn't leak at all.
  • Listen and feel. A sound like gravel rattling through the pump is cavitation, caused by too little suction pressure (NPSH), and it pits impellers. Rising vibration or hot bearings mean wear or misalignment.
  • Mind the valves. Never close the discharge of a positive displacement pump while it runs. A centrifugal pump can run briefly against a closed discharge, but the trapped water heats up fast. Don't throttle a pump on its suction side.
  • Prevent water hammer. Open and close valves slowly, and keep check valves and surge equipment working, because a sudden stop sends a pressure wave through the pipe.
  • Keep records. Log run hours, amps, discharge pressure, and flow. Less flow at the same pressure is often the first sign of a worn impeller or a clogged well screen.
Go deeper: Hydraulic ModelingChange a pipe or a pump and watch a live town network re-solve, then try the pump curve lab, fire flow test, and water hammer calculators.

📌 Numbers Greg wants you to memorize

  • 1 ft of water = 0.433 psi — the core static-pressure conversion.
  • 1 psi = 2.31 ft of water — the reverse conversion.
  • 62.4 lbs/ft³ — the weight (specific weight) of water.
  • Design distribution velocities stay under 5 ft/sec to minimize friction loss.
  • Hazen-Williams C-factor: new PVC ≈ 150, new ductile iron ≈ 130, old cast iron can fall below 50.
  • Water hp = gpm × TDH ÷ 3,960; brake hp = water hp ÷ pump efficiency.
  • 1 hp = 0.746 kW.
  • Affinity laws: flow ∝ speed, head ∝ speed², power ∝ speed³.
Key terms

Words to know for Chapter 4

Plain-language definitions from the LearnWater glossary.

Open the full glossary →

Check yourself

Quick check: 5 questions

Random questions from this chapter's bank. Your answers count toward your progress in the Learning Center.

Flash cards

Tap a card to flip it

Study these in the flash card trainer →